| SIMOCON |
| fixed-mounted / plug-in switchgear for LV-Distributions, MCC, PLC Systems |
| |
 |
SIMOCON® has proven long-term reliability and success distinguishing itself by its high flexibility, quality and efficiency. Type tested at 80 KA / 1s.
SIMOCON® is suitable for power levels up to Return: 660 VAC 50-60 Hz including power distribution, power change-over, power compensation and lighting systems.
According to customers needs it can be installed in either fixed-mounted or plug-in design. |
| |
 |
Providing and organizing the power, it represents the heart in industrial plants, airports, hospitals, office tower and power stations.
SIMOCON® is constructed in accordance with German and Chinese standards, including IEC 60439-1 and GB 7251.1-97. |
|
|
For the following applications both, fixed-mounted and plugin design is suitable:
Low Voltage distribution systems
Power Control Center
Motor Control Center
Lighting systems
|
|
Passed CCC Test by China Quality Certification Center
Passed inner Arc-fault Test
|
| |
| Technical Data |
| Standards and Specifications |
IEC 60439-1, DIN EN 60439-1 (VDE 0660 Part 500)
Chinese GB 725/-97, ZBK 36001-89 |
| Rated insulation voltage(Ui) |
660 V |
| Rated operational voltage(Ue) |
380 V, 690 V |
| Main horizontal busbar |
| Rated Current |
4000A |
| Rated peak withstand current(Ipk) |
176 kA |
| Rated short-time withstand current(Icw) |
80 kA/1s |
| Degree of Protection |
IP 30 - IP 54 |
| Ambient Temperature |
40 ºC max. / 35 ºC avg. |
| Dimensions |
| Height |
2200 mm |
| Width |
1000 mm |
| Depth |
600 mm |
|
| |
 SIMOCON Catalogue (EN/CN) |